Input data
AC operation | |
Nominal input voltage range | 100 V AC ... 277 V AC |
Input voltage range | 85 V AC ... 305 V AC |
95 V DC ... 250 V DC | |
Input voltage range AC | 85 V AC ... 305 V AC |
Input voltage range DC | 95 V DC ... 250 V DC |
Voltage type of supply voltage | AC/DC |
Inrush current | < 40 A (typical) |
Inrush current integral (I2t) | < 2.8 A2s |
AC frequency range | 45 Hz ... 65 Hz |
Frequency range DC | 0 Hz |
Mains buffering time | typ. 25 ms (120 V AC) |
typ. 160 ms (277 V AC) | |
Current consumption | 1.43 A (120 V AC) |
0.75 A (277 V AC) | |
Nominal power consumption | 147.7 VA |
Power factor (cos phi) | 0.64 |
Typical response time | < 0.5 s |
Input fuse | 4 A (slow-blow, internal) |
Permissible backup fuse | B6 B10 B16 |
Recommended breaker for input protection | 6 A ... 16 A (Characteristics B, C, D, K) |
Efficiency | > 88 % (for 277 V AC and nominal values) |
Output characteristic | U/I |
Nominal output voltage | 24 V DC ±1 % |
Setting range of the output voltage (USet) | 22.5 V DC ... 25 V DC (> 24 V DC, constant capacity restricted) |
Output current Imax | 6 A |
Nominal output current (IN) | 3.5 A (-25 °C ... 55 °C) |
Derating | 55 °C ... 70 °C (2.5%/K) |
Feedback voltage resistance | ≤ 35 V DC |
Protection against overvoltage at the output (OVP) | < 35 V DC |
Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
< 2 % (change in load, dynamic 10 % ... 90 %) | |
< 0.1 % (change in input voltage ±10 %) | |
Residual ripple | < 10 mVPP (20 MHz) |
Output power | 84 W |
Peak switching voltages nominal load | < 30 mVPP (20 MHz) |
Maximum no-load power dissipation | < 0.6 W |
Power loss nominal load max. | 11.5 W |
Rise time | < 0.5 s (UOUT (10 % ... 90 %)) |
Connection in series | yes |