Input data
AC operation | |
Supply system configuration | Star network (TN, TT, IT (PE)) |
Input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % |
Typical national grid voltage | 120 V AC |
230 V AC | |
Voltage type of supply voltage | AC/DC |
Inrush current | typ. 27 A (25 °C) |
Inrush current integral (I2t) | typ. 0.12 A2s |
Frequency range (fN) | 50 Hz ... 60 Hz ±10 % |
Mains buffering time | typ. 20 ms (120 V AC) |
typ. 85 ms (230 V AC) | |
Current consumption | 0.3 A (100 V AC) |
0.17 A (240 V AC) | |
Switch-on time | typ. 2 s |
Device mains fuse | 1.25 A internal (device protection), slow-blow |
Recommended breaker for input protection | 6 A ... 16 A (Characteristics B, C, D, K) |
Discharge current to PE | < 0.25 mA |
DC operation | |
Input voltage range | 110 V DC ... 250 V DC -20 % ... +10 % |
Current consumption | 0.17 A (110 V DC) |
0.08 A (250 V DC) |
Efficiency | > 85.5 % (120 V AC) |
> 86 % (230 V AC) | |
Efficiency Level | VI |
Nominal output voltage | 12 V DC |
Nominal output current (IN) | 1.3 A |
Short-circuit-proof | yes |
No-load proof | yes |
Derating | > 50 °C ... 70 °C (2 % / K) |
Crest factor | typ. 3.43 |
typ. 4.5 | |
Output power (PN) | 15 W |
Connection in parallel | yes, for increasing power and redundancy with diode |
Connection in series | yes, for increased output voltage |
Feedback voltage resistance | ≤ 25 V DC |
Protection against overvoltage at the output (OVP) | < 25 V DC |
Residual ripple | typ. 150 mVPP |
Control deviation | < 1 % (Static load change 10 % ... 90 %) |
< 4 % (Dynamic load change 10 % ... 90 %, (10 Hz)) | |
< 0.1 % (change in input voltage ±10 %) | |
Rise time | typ. 100 ms (UOut = 10 % ... 90 %) |
Minimum no-load power dissipation | < 0.1 W (120 V AC) |
Maximum no-load power dissipation | < 0.1 W (230 V AC) |
Minimum nominal load power dissipation | < 3.2 W (120 V AC) |
Power loss nominal load max. | < 3 W (230 V AC) |