| Feature | Value |
|---|---|
| Size | 6 |
| Series | MS |
| Assembly position | Any Preferably vertical |
| Design structure | Electrically adjustable pressure regulator |
| Short circuit strength | for all electrical connections |
| Controller function | Output pressure constant with initial pressure compensation with secondary exhaust |
| Pressure gauge | Optional With display and control unit with pressure gauge |
| Operating pressure | 0.8 ... 20 bar |
| Pressure regulation range | 0.3 ... 16 bar |
| Max. pressure hysteresis | 0.25 bar |
| Standard nominal flow rate | 2,200 ... 7,500 l/min |
| Analogue output | 0 - 10 V 4 - 20 mA |
| Duration of control at 25°C | Max. 90 s |
| Type of inputs | Per IEC 61131-2 No electrical isolation |
| Nominal operating voltage DC | 24 V |
| Current consumption at nominal operating voltage | Max. 1 A |
| Current consumption | Max 3.5 A at 24 V DC |
| Control duration/ interval ratio | 1:3 |
| Permissible voltage fluctuation | +/- 10 % |
| Authorisation | c UL us - Recognized (OL) |
| CE mark (see declaration of conformity) | to EU directive for EMC |
| Operating medium | Compressed air in accordance with ISO8573-1:2010 [7:4:4] Inert gases |
| Note on operating and pilot medium | Lubricated operation possible (subsequently required for further operation) |
| Corrosion resistance classification CRC | 2 - Moderate corrosion stress |
| Storage temperature | -10 ... 50 °C |
| Food-safe | See Supplementary material information |
| Medium temperature | 0 ... 50 °C |
| Protection class | IP65 |
| Ambient temperature | 0 ... 50 °C |
| Product weight | 1,820 g |
| Analogue outputs, absolute accuracy at 25° C | ± 3% |
| Cable interface | Input: M12x1 plug, 5-pin Output: M8x1 plug, 3-pin |
| Mounting type | Optional Line installation On sub-base with wall/surface fixing with accessories |
| Material operator unit | PA |
| Material seals | NBR |
| Material housing | Aluminium die cast |
| Material membrane | NBR |

.jpg)