Input:
Output:
| Efficiency | 85 % (115 V AC) |
| 88 % (230 V AC) | |
| Output characteristic | HICCUP |
| Nominal output voltage | 24 V DC ±2 % |
| Setting range of the output voltage (USet) | 22 V DC ... 28 V DC (max. power ≤ 120 W) |
| Nominal output current (IN) | 5 A |
| Derating | -20 °C ... -10 °C (2 % / °C) |
| > 40 °C (1.67 % / °C, 115 V AC) | |
| > 50 °C (2.5 % / °C, 230 V AC) | |
| Max. capacitive load | 8000 μF |
| Active current limitation | 105% - 150% of the max. output power (in the event of short circuit) |
| Control deviation | ≤ 1 % (change in load, static 10 % ... 90 %) |
| typ. ± 2 % (change in load, dynamic 10 % ... 90 %) | |
| < 0.1 % (change in input voltage ±10 %) | |
| Residual ripple | < 120 mVPP (-10 °C ... +70 °C) |
| < 240 mVPP (-20 °C ... -10 °C) | |
| Output power | 120 W |
| Maximum no-load power dissipation | 0.65 W (115 V AC / 230 V AC) |
| Power loss nominal load max. | 13.3 W (115 V AC / 230 V AC) |
| Rise time | typ. 30 ms (at nominal load) |