Input Data
| Nominal input voltage range | 24 V DC ... 48 V DC |
| Input voltage range | 24 V DC ... 48 V DC -10 % ... +25 % |
| Wide-range input | yes |
| Electric strength, max. | 60 V DC (60 s) |
| Inrush current | typ. 8 A |
| Inrush current integral (I2t) | typ. 0.1 A2s |
| Inrush current limitation | 8 A |
| Mains buffering time | typ. 13 ms (24 V DC) |
| typ. 18 ms (48 V DC) | |
| > 20 ms (24 V DC / 48 V DC, at 50% load) | |
| Current consumption | typ. 5.6 A (24 V DC) |
| typ. 2.7 A (48 V DC) | |
| Switch-on time | < 1 s |
| Input fuse | 15 A (slow-blow, internal) |
| Recommended breaker for input protection | 10 A ... 16 A (Characteristic B, C, D, K or comparable) |
| Efficiency | typ. 90.1 % (24 V DC) |
| typ. 91.9 % (48 V DC) | |
| Output characteristic | U/I Advanced |
| Smart HICCUP | |
| FUSE MODE | |
| Nominal output voltage | 48 V DC |
| Setting range of the output voltage (USet) | 48 V DC ... 56 V DC (> 48 V constant capacity) |
| Nominal output current (IN) | 2 A |
| Static Boost (IStat.Boost) | 2.5 A |
| Dynamic Boost (IDyn.Boost) | 4 A (4.9 s) |
| Short-circuit-proof | yes |
| No-load proof | yes |
| Derating | > 60 °C (2.5%/K of POut nom.) |
| Output power (PN) | 96 W |
| Output power (PStat. Boost) | 120 W |
| Output power (PDyn. Boost) | 192 W |
| Feedback voltage resistance | ≤ 65 V DC |
| Protection against overvoltage at the output (OVP) | ≤ 60 V DC |
| Residual ripple | < 20 mVPP |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
| Rise time | < 1 s (UOUT (10 % ... 90 %)) |
| Connection in series | yes |
| Maximum no-load power dissipation | < 2.5 W |
| Power loss nominal load max. | < 7.5 W |
| Connection in parallel | yes, for redundancy and increased capacity |
| Signal (configurable) | |
| Digital | 0 V DC |
| 24 V DC | |
| 22 mA | |
| Default | 24 V DC |
| 22 mA | |
| 24 V DC for UOut > 0.9 x USet | |

.jpg)