| Efficiency |
> 89 % |
| Output characteristic |
U/I |
| Nominal output voltage |
12 V DC ±1 % |
| Setting range of the output voltage (USet) |
5 V DC ... 18 V DC (> 12 V DC, constant capacity restricted) |
| Nominal output current (IN) |
8 A (-25 °C ... 60 °C) |
| POWER BOOST (IBoost) |
10 A (-25 °C ... 40 °C permanent, UOUT = 12 V DC ) |
| Selective Fuse Breaking (ISFB) |
48 A (12 ms) |
| Magnetic circuit breaker tripping |
B2 / B4 / C2 |
| Derating |
60 °C ... 70 °C (2.5%/K) |
| Feedback voltage resistance |
25 V DC |
| Protection against overvoltage at the output (OVP) |
< 25 V DC |
| Max. capacitive load |
unlimited |
| Active current limitation |
15 A |
| Control deviation |
< 1 % (change in load, static 10 % ... 90 %) |
| < 2 % (change in load, dynamic 10 % ... 90 %) |
| < 0.1 % (change in input voltage ±10 %) |
| Residual ripple |
< 20 mVPP |
| Output power |
96 W |
| Peak switching voltages nominal load |
< 10 mVPP (20 MHz) |
| Maximum no-load power dissipation |
1.5 W |
| Power loss nominal load max. |
11.8 W |
| Rise time |
< 2 ms (UOUT (10 % ... 90 %)) |
| Connection in parallel |
yes, for redundancy and increased capacity |
| Connection in series |
yes |
| Signal: DC OK active |
| Output description |
UOUT > 0.9 x UN: High signal |
| Switching voltage range |
12 V DC |
| Maximum inrush current |
< 20 mA (short-circuit-proof) |
| Signal: POWER BOOST, active |
| Output description |
IOUT < IN: High signal |
| Switching voltage range |
12 V DC |
| Maximum inrush current |
< 20 mA (short-circuit-proof) |
| Signal: UIN OK, active |
| Output description |
UIN > 9.6 V: high signal |
| Switching voltage range |
12 V DC |
| Maximum inrush current |
≤ 20 mA (short-circuit-proof) |