Input data
| AC operation | |
| Nominal input voltage range | 100 V AC ... 240 V AC |
| Input voltage range | 85 V AC ... 264 V AC |
| 95 V DC ... 250 V DC | |
| Input voltage range AC | 85 V AC ... 264 V AC |
| Input voltage range DC | 95 V DC ... 250 V DC |
| Voltage type of supply voltage | AC/DC |
| Inrush current | < 15 A |
| Inrush current integral (I2t) | < 0.1 A2s |
| AC frequency range | 45 Hz ... 65 Hz |
| Frequency range DC | 0 Hz |
| Mains buffering time | typ. 25 ms (120 V AC) |
| typ. 110 ms (230 V AC) | |
| Current consumption | 0.2 A (120 V AC) |
| 0.13 A (230 V AC) | |
| Nominal power consumption | 28.9 VA |
| Power factor (cos phi) | 0.44 |
| Typical response time | < 0.5 s |
| Input fuse | 1.25 A (slow-blow, internal) |
| Permissible DC backup fuse | DC: Connect a suitable fuse upstream |
| Recommended breaker for input protection | 6 A ... 16 A (AC: Characteristics B, C, D, K) |
| Efficiency | > 81 % (for 230 V AC and nominal values) |
| Output characteristic | U/I |
| Nominal output voltage | 5 V DC ±1 % |
| Output current Imax | 3.7 A |
| Nominal output current (IN) | 2 A (-25 °C ... 40 °C permanent) |
| 2.2 A (-25 °C ... 55 °C) | |
| Derating | 55 °C ... 70 °C (2.5%/K) |
| Protection against overvoltage at the output (OVP) | < 10 V DC |
| Residual ripple | < 50 mVPP |
| Output power | 10 W |
| Maximum no-load power dissipation | < 0.4 W |
| Power loss nominal load max. | < 2.6 W |
| Connection in parallel | yes, for redundancy and increased capacity |
| Connection in series | yes |

.jpg)