Bộ nguồn đầu vào 3AC, đầu ra 24VDC, 5A 2866462

Bộ nguồn đầu vào 3AC, đầu ra 24VDC, 5A 2866462

Mã sản phẩm: 2866462

Mã hàng: TRIO-PS/3AC/24DC/ 5

Xuất xứ: Trung Quốc

MVN cam kết sản phẩm 100% chính hãng, có xuất xứ, CO, CQ đầy đủ

Thông tin chi tiết sản phẩm

 

AC operation
Nominal input voltage range 2x / 3x 400 V AC ... 500 V AC
Input voltage range 3x 320 V AC ... 575 V AC (for 3-phase operation)
2x 360 V AC ... 575 V AC (for 2-phase operation)
Input voltage range AC 3x 320 V AC ... 575 V AC (for 3-phase operation)
2x 360 V AC ... 575 V AC (for 2-phase operation)
Voltage type of supply voltage AC
Inrush current < 15 A
Inrush current integral (I2t) 0.2 A2s
AC frequency range 45 Hz ... 65 Hz
Mains buffering time > 20 ms (3x 400 V AC)
> 30 ms (3x 480 V AC)
Current consumption 3x 0.3 A (400 V AC)
3x 0.25 A (500 V AC)
2x 0.65 A (400 V AC)
2x 0.5 A (500 V AC)
Nominal power consumption 211 VA
Protective circuit Transient surge protection; Varistor
Power factor (cos phi) 0.64
Typical response time < 1 s
Permissible backup fuse B6 B10 B16
Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
Discharge current to PE < 3.5 mA

Efficiency 89 % (at 400 V AC and nominal values)
Output characteristic U/I
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 22.5 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 5 A (UOUT = 24 V DC)
Derating 55 °C ... 70 °C (2.5%/K)
Feedback voltage resistance 35 V DC
Protection against overvoltage at the output (OVP) < 35 V DC
Max. capacitive load unlimited
Active current limitation Approx 6 A (in the event of a short-circuit)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 30 mVPP
Output power 120 W
Peak switching voltages nominal load < 30 mVPP
Maximum no-load power dissipation 4 W
Power loss nominal load max. 15 W
Rise time < 2 ms (UOUT (10 % ... 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes

Input
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 9 mm
Screw thread M2,5
Tightening torque, min 0.4 Nm
Tightening torque max 0.5 Nm
Output
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 16
Conductor cross section AWG max. 12
Stripping length 9 mm
Screw thread M2,5
Tightening torque, min 0.4 Nm
Tightening torque max 0.5 Nm

Types of signaling LED
Operating voltage display Green LED
Signal output
Status display "DC OK" LED green
Note on status display UOUT > 21.5 V: LED lights up

Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE 500 V DC (routine test)
Insulation voltage input / PE 2 kV AC (type test)
2 kV AC (routine test)

Product type Power supply
MTBF (IEC 61709, SN 29500) > 1474000 h
Insulation characteristics
Protection class I (with PE connection)
Overvoltage category III
Degree of pollution 2

Width 40 mm
Height 130 mm
Depth 115 mm
Installation dimensions
Installation distance right/left 0 mm / 0 mm
Installation distance top/bottom 50 mm / 50 mm

Assembly instructions alignable: horizontally 0 mm, vertically 50 mm
Mounting position horizontal DIN rail NS 35, EN 60715

Color aluminium
Type of housing Steel sheet, zinc-plated
Side element version Aluminum

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 55° C derating : 2.5%/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Shock 15g in all directions in acc. with IEC 60068-2-27
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.

Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment EN 50178
Standard – Safety extra-low voltage EN 60950-1 (SELV)
EN 60204 (PELV)
Standard - Safe isolation DIN VDE 0100-410

UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
Conformity/Approvals
SIL in accordance with IEC 61508 0

Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
Noise immunity EN 61000-6-2:2005
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 8 kV (Test Level 4)
Discharge in air 8 kV (Test Level 3)
Comments Criterion A
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 1 GHz
Test field strength 10 V/m
Frequency range 1 GHz ... 2 GHz
Test field strength 10 V/m
Frequency range 2 GHz ... 3 GHz
Test field strength 10 V/m
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 4 kV (Test Level 4 - asymmetrical)
Output 4 kV (Test Level 4 - asymmetrical)
Signal 2 kV (Test Level 3 - asymmetrical)
Comments Criterion A
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Input 2 kV (Test Level 3 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Comments Criterion A
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
Frequency range 0.15 MHz ... 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)
Conducted interference
Frequency range 0.15 MHz ... 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)
Voltage dips
Standards/regulations EN 61000-4-11
Emitted interference
Standards/regulations EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential