Input
| DC operation | |
| Nominal input voltage range | 500 V DC ... 1500 V DC |
| Input voltage range | 450 V DC ... 1650 V DC |
| Wide-range input | no |
| Electric strength, max. | ≤ 1800 V DC 1 s |
| Typical national grid voltage | 500 V DC |
| 1500 V DC | |
| Voltage type of supply voltage | DC |
| Inrush current integral (I2t) | typ. 0.15 A2s |
| Current consumption | typ. 85 mA (450 V DC) |
| typ. 30 mA (1500 V DC) | |
| Recommended breaker for input protection | 2 A (1500 V DC) |
| Efficiency | typ. 88 % (500 V DC) |
| typ. 87 % (900 V DC) | |
| typ. 83 % (1500 V DC) | |
| Nominal output voltage | 24 V DC ±3 % |
| Nominal output current (IN) | 1.5 A |
| Derating | > 60 °C ... 70 °C (2.5%/K) |
| Feedback voltage resistance | ≤ 35 V DC |
| Protection against overvoltage at the output (OVP) | ≤ 30 V DC |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
| < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) | |
| < 0.1 % (change in input voltage ±10 %) | |
| Residual ripple | < 40 mVPP (Ripple) |
| < 50 mVPP (Noise) | |
| Short-circuit-proof | yes |
| No-load proof | yes |
| Output power | 36 W |
| Maximum no-load power dissipation | < 1.1 W (500 V DC) |
| < 1.4 W (900 V DC) | |
| < 2.4 W (1500 V DC) | |
| Power loss nominal load max. | < 4.2 W (500 V DC) |
| < 5.5 W (900 V DC) | |
| < 7.5 W (1500 V DC) | |
| Rise time | ≤ 30 ms (UOUT (10 % ... 90 %)) |
| Connection in parallel | yes, for redundancy and increased capacity |
| Connection in series | No |