Diode - QUINT-DIODE/48DC/2X20/1X40 - 2320160 - PHOENIX CONTACT

Tên sản phẩm:    Nguồn DIODE 

Nhãn: Phoenix contact

Mã sản phẩm: 2320160  // 1 số mã sản phẩm diode 

TT Order No                         Product Code
1 2868606                   STEP-DIODE/5-24DC/2X5/1X10
2 2905489                   UNO-DIODE/5-24DC/2X10/1X20
3 2866527                  TRIO-DIODE/48DC/2X10/1X20
4 2907720                   QUINT4-DIODE/48DC/2X20/1X40
5 2938963                   QUINT-DIODE/40 
6 2866585                   QUINT-DIODE/48DC/40
7 2320157                   QUINT-DIODE/12-24DC/2X20/1X40
8 2320173                   QUINT-ORING/24DC/2X10/1X20
9 2320186                   QUINT-ORING/24DC/2X20/1X40
10 2902879                   QUINT-ORING/24DC/2X40/1X80
11 2320160                   QUINT-DIODE/48DC/2X20/1X40
12 2866514                   TRIO-DIODE/12-24DC/2X10/1X20
13 2907379                   TRIO2-DIODE/12-24DC/2X20/1X40
14 2907380                   TRIO2-DIODE/12-24DC/2X10/1X20
15 2907719                    QUINT4-DIODE/12-24DC/2X20/1X40
16 2907752                    QUINT4-S-ORING/12-24DC/1X40
17 2907753                   QUINT4-S-ORING/12-24DC/1X40/+
 

Diode - QUINT-DIODE/48DC/2X20/1X40 - 2320160 - PHOENIX CONTACT 

Phoenix contact / 2320160 / 

/MVN/ 

 

Thông tin chi tiết sản phẩm

Country of origin CN (China) 

Dimensions
Width 50 mm
Height 130 mm
Depth 125 mm
Installation distance right/left 5 mm / 5 mm
Installation distance top/bottom 50 mm / 50 mm
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Installation height 2000 m
Input data
Nominal input voltage range 48 V DC
48 V DC
Input voltage range 30 V DC ... 56 V DC
30 V DC ... 56 V DC
Nominal input current 2x 20 A (-25 °C ... 60 °C)
1x 40 A (-25 °C ... 60 °C)
Maximum input current 2x 30 A (-25°C ... 40°C)
1x 60 A (-25°C ... 40°C)
Nominal input current 2x 20 A (-25 °C ... 60 °C)
1x 40 A (-25 °C ... 60 °C)
Maximum input current 2x 30 A (-25°C ... 40°C)
1x 60 A (-25°C ... 40°C)
Output data
Nominal output voltage 48 V DC
Nominal output current (IN) 40 A (Increasing power)
20 A (Redundancy)
Derating 60 °C ... 70 °C (2.5%/K)
Connection in series No
Power loss nominal load max. 14 W (IOUT = 20 A
Connection data, output
Connection method Screw connection
Conductor cross section solid min. 0.5 mm²
Conductor cross section solid max. 16 mm²
Conductor cross section flexible min. 0.5 mm²
Conductor cross section flexible max. 16 mm²
Conductor cross section AWG min. 10
Conductor cross section AWG max. 6
Stripping length 10 mm
Screw thread M4