Tài liệu kỹ thuật
[↓ Tải xuống]
Product properties
Product type
Ground terminal block
Area of application
Railway industry
Machine building
Plant engineering
Process industry
Number of connections
2
Number of rows
1
Insulation characteristics
Overvoltage category
III
Degree of pollution
3
Electrical properties
Rated surge voltage
8 kV
Maximum power dissipation for nominal condition
1.82 W
Connection data
Grounding foot
Yes
Number of connections per level
2
Nominal cross section
10 mm²
Level 1 above 1 below 1
Screw thread
M4
Note
Please observe the current carrying capacity of the DIN rails.
Tightening torque
1.5 ... 1.8 Nm
Stripping length
10 mm
Internal cylindrical gage
A6
Connection in acc. with standard
IEC 60947-7-2
Conductor cross section solid
0.5 mm² ... 16 mm²
Cross section AWG
20 ... 6
Conductor cross section flexible
0.5 mm² ... 16 mm²
Conductor cross section, flexible [AWG]
20 ... 6
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve)
0.5 mm² ... 10 mm²
Flexible conductor cross section (ferrule with plastic sleeve)
0.5 mm² ... 10 mm²
Note
Note: Product releases, connection cross sections and notes on connecting aluminum cables can be found in the download area.
Nominal cross section
10 mm²
Ex data
Rated data (ATEX/IECEx)
ATEX certificate
KEMA 04 ATEX 2048 U
IEC Ex certificate
IECEx KEM 06.0027 U
Identification
Ex eb IIC Gb
Operating temperature range
-60 °C ... 110 °C
Ex-certified accessories
3047028 D-UT 2,5/10
1205066 SZS 1,0X4,0 VDE
3022276 CLIPFIX 35-5
3022218 CLIPFIX 35
Ex connection data General
Torque range
1.5 Nm ... 1.8 Nm
Nominal cross section
10 mm²
Rated cross section AWG
8
Connection capacity rigid
0.5 mm² ... 16 mm²
Connection capacity AWG
20 ... 6
Connection capacity flexible
0.5 mm² ... 10 mm²
Connection capacity AWG
20 ... 8
Dimensions
Width
10.2 mm
End cover width
2.2 mm
Height
46.9 mm
Height NS 35/15
55 mm
Height NS 35/7,5
47.5 mm
Length
47.7 mm
Material specifications
Color
green-yellow
Flammability rating according to UL 94
V0
Insulating material group
I
Insulating material
PA
Static insulating material application in cold
-60 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
125 °C
Relative insulation material temperature index (Elec., UL 746 B)
130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Calorimetric heat release NFPA 130 (ASTM E 1354)
27,5 MJ/kg
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Mechanical properties
Mechanical data
Open side panel
Yes
Environmental and real-life conditions
Oscillation/broadband noise
Specification
DIN EN 50155 (VDE 0115-200):2018-05
Spectrum
Service life test category 2, bogie-mounted
Frequency
f1 = 5 Hz to f2 = 250 Hz
ASD level
6.12 (m/s²)²/Hz
Acceleration
3.12g
Test duration per axis
5 h
Test directions
X-, Y- and Z-axis
Shocks
Specification
DIN EN 50155 (VDE 0115-200):2008-03
Pulse shape
Half-sine
Acceleration
30g
Shock duration
18 ms
Number of shocks per direction
3
Test directions
X-, Y- and Z-axis (pos. and neg.)
Ambient conditions
Ambient temperature (operation)
-60 °C ... 105 °C (max. short-term operating temperature RTI Elec.)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Permissible humidity (storage/transport)
30 % ... 70 %
Standards and regulations
Connection in acc. with standard
IEC 60947-7-2
Mounting
Mounting type
NS 35/7,5
NS 35/15