| Shipping date |
View |
| Valve function |
5/2 bistable |
| Type of actuation |
electrical |
| Width |
32 mm |
| Standard nominal flow rate |
1,350 l/min |
| Operating pressure |
1.5 ... 8 bar |
| Design structure |
Piston slide |
| Explosion protection certification outside the EU |
EPL Db (IEC-EX)
EPL Ga (IEC-EX) |
| Certificate issuing department |
DNVGL-TAA000011J |
| ATEX category Gas |
II 2G |
| ATEX category Dust |
II 2D |
| Explosion ignition protection type Gas |
Ex ia IIC T6 Ga |
| Explosion ignition protection type Dust |
Ex t IIIC T80°C Db |
| Explosion-proof ambient temperature |
-40°C <= Ta <= +50°C |
| Protection class |
IP65
with plug socket
to IEC 60529 |
| Exhaust-air function |
throttleable |
| Sealing principle |
soft |
| Assembly position |
Any |
| Conforms to standard |
VDI/VDE 3845 (NAMUR) |
| Manual override |
detenting
Pushing |
| Type of piloting |
Piloted |
| Pilot air supply |
Internal |
| Flow direction |
non reversible |
| Overlap |
Positive overlap |
| Signal status display |
with accessories |
| b value |
0.4 |
| C value |
5.6 l/sbar |
| Switching time reversal |
20 ms |
| Duty cycle |
100 % |
| Max. input voltage |
28 V |
| Max. input current |
115 mA |
| Permissible voltage fluctuation |
+/- 10 % |
| Operating medium |
Compressed air in accordance with ISO8573-1:2010 [7:4:4] |
| Note on operating and pilot medium |
Lubricated operation possible (subsequently required for further operation) |
| Corrosion resistance classification CRC |
2 - Moderate corrosion stress |
| Medium temperature |
-20 ... 60 °C |
| Ambient temperature |
-20 ... 60 °C |
| Product weight |
685 g |
| Electrical connection |
to EN 175301-803
Plug pattern type A to EN 175301-803 |
| Mounting type |
with through hole |
| Scavenging orifice connection |
Non-ducted |
| Pneumatic connection, port 1 |
G1/4 |
| Pneumatic connection, port 2 |
NAMUR port pattern |
| Pneumatic connection, port 3 |
G1/4 |
| Pneumatic connection, port 4 |
NAMUR port pattern |
| Pneumatic connection, port 5 |
G1/4 |