Notes
General
The current is determined by the fuse used, the voltage by the selected LED.
If the fuse is faulty, the downstream circuit will not be disconnected.
Product properties
Product type
Fuse terminal block
Number of connections
2
Number of rows
1
Potentials
1
Insulation characteristics
Overvoltage category
III
Degree of pollution
3
Electrical properties
Fuse type
Glass / ceramics / ...
Rated surge voltage
4 kV
Maximum power dissipation for nominal condition
1.02 W
Fuse
G / 5 x 20
LED voltage range
12 V AC/DC ... 30 V AC/DC
LED current range
0.31 mA ... 0.95 mA
Maximum power dissipation
max. 1.6 W (with single arrangement of the fuse terminal block in the event of overload)
max. 1.6 W (With interconnected arrangement of several fuse terminal blocks in the event of overload)
max. 4 W (with single arrangement of the fuse terminal block in the event of a short-circuit)
max. 2.5 W (With interconnected arrangement of several fuse terminal blocks in the event of a short-circuit)
Input data
LED voltage range
12 V AC/DC ... 30 V AC/DC
Connection data
Number of connections per level
2
Nominal cross section
4 mm²
1 level
Stripping length
8 mm
Internal cylindrical gage
A4
Connection in acc. with standard
IEC 60947-7-3
Conductor cross section solid
0.08 mm² ... 6 mm²
Cross section AWG
28 ... 10
Conductor cross section flexible
0.08 mm² ... 4 mm²
Conductor cross section, flexible [AWG]
28 ... 12
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve)
0.14 mm² ... 4 mm²
Flexible conductor cross section (ferrule with plastic sleeve)
0.14 mm² ... 4 mm²
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve
0.5 mm² ... 1 mm²
Nominal current
6.3 A
Maximum load current
6.3 A (the current is determined by the fuse used)
Nominal voltage
24 V
Nominal cross section
1 mm²
Dimensions
Width
6.2 mm
Height NS 35/15
70 mm
Height NS 35/7,5
62.5 mm
Length
61.5 mm
Material specifications
Color
black
Flammability rating according to UL 94
V0
Insulating material group
I
Insulating material
PA
Static insulating material application in cold
-60 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
130 °C
Relative insulation material temperature index (Elec., UL 746 B)
130 °C
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 3
Calorimetric heat release NFPA 130 (ASTM E 1354)
28 MJ/kg
Surface flammability NFPA 130 (ASTM E 162)
passed
Specific optical density of smoke NFPA 130 (ASTM E 662)
passed
Smoke gas toxicity NFPA 130 (SMP 800C)
passed
Electrical tests
Surge voltage test
Result
Test passed
Temperature-rise test
Requirement temperature-rise test
Increase in temperature ≤ 45 K
Result
Test passed
Result
Test passed
Power-frequency withstand voltage
Test voltage setpoint
1.89 kV
Result
Test passed
Mechanical properties
Mechanical data
Open side panel
No
Mechanical tests
Mechanical strength
Result
Test passed
Attachment on the carrier
Result
Test passed
Test for conductor damage and slackening
Rotation speed
10 (+/- 2) rpm
Revolutions
135
Conductor cross section/weight
4 mm² / 0.9 kg
Result
Test passed
Environmental and real-life conditions
Aging
Temperature cycles
192
192
192
Result
Test passed
Test passed
Needle-flame test
Time of exposure
30 s
Result
Test passed
Oscillation/broadband noise
Spectrum
Service life test category 2, bogie-mounted
Frequency
5 - 250 Hz
ASD level
6.12 (m/s²)²/Hz
Acceleration
3.12g
Test duration per axis
5 h
Test directions
X-, Y- and Z-axis
Result
Test passed
Shocks
Pulse shape
Half-sine
Acceleration
30g
Shock duration
18 ms
Number of shocks per direction
3
Test directions
X-, Y- and Z-axis (pos. and neg.)
Result
Test passed
Ambient conditions
Ambient temperature (operation)
-60 °C ... 105 °C (max. short-term operating temperature RTI Elec.)
Ambient temperature (storage/transport)
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Ambient temperature (assembly)
-5 °C ... 70 °C
Ambient temperature (actuation)
-5 °C ... 70 °C
Permissible humidity (storage/transport)
30 % ... 70 %
Standards and regulations
Connection in acc. with standard
IEC 60947-7-3
Mounting
Mounting type
NS 35/7,5
NS 35/15