General |
The current is determined by the fuse used, the voltage by the selected LED.
If the fuse is faulty, the downstream circuit will not be disconnected. |
Product type |
Fuse terminal block |
Number of connections |
2 |
Number of rows |
1 |
Potentials |
1 |
Insulation characteristics |
Overvoltage category |
III |
Degree of pollution |
3 |
Fuse type |
Glass / ceramics / ... |
Rated surge voltage |
4 kV |
Maximum power dissipation for nominal condition |
1.02 W |
Fuse |
G / 5 x 20 |
LED voltage range |
12 V AC/DC ... 30 V AC/DC |
LED current range |
0.31 mA ... 0.95 mA |
Maximum power dissipation |
max. 1.6 W (with single arrangement of the fuse terminal block in the event of overload) |
max. 1.6 W (With interconnected arrangement of several fuse terminal blocks in the event of overload) |
max. 4 W (with single arrangement of the fuse terminal block in the event of a short-circuit) |
max. 2.5 W (With interconnected arrangement of several fuse terminal blocks in the event of a short-circuit) |
LED voltage range |
12 V AC/DC ... 30 V AC/DC |
Number of connections per level |
2 |
Nominal cross section |
4 mm² |
1 level |
Stripping length |
8 mm |
Internal cylindrical gage |
A4 |
Connection in acc. with standard |
IEC 60947-7-3 |
Conductor cross section solid |
0.08 mm² ... 6 mm² |
Cross section AWG |
28 ... 10 |
Conductor cross section flexible |
0.08 mm² ... 4 mm² |
Conductor cross section, flexible [AWG] |
28 ... 12 |
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve) |
0.14 mm² ... 4 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) |
0.14 mm² ... 4 mm² |
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve |
0.5 mm² ... 1 mm² |
Nominal current |
6.3 A |
Maximum load current |
6.3 A (the current is determined by the fuse used) |
Nominal voltage |
24 V |
Nominal cross section |
1 mm² |
Width |
6.2 mm |
Height NS 35/15 |
70 mm |
Height NS 35/7,5 |
62.5 mm |
Length |
61.5 mm |
Color |
black |
Flammability rating according to UL 94 |
V0 |
Insulating material group |
I |
Insulating material |
PA |
Static insulating material application in cold |
-60 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) |
130 °C |
Relative insulation material temperature index (Elec., UL 746 B) |
130 °C |
Fire protection for rail vehicles (DIN EN 45545-2) R22 |
HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 |
HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 |
HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 |
HL 1 - HL 3 |
Calorimetric heat release NFPA 130 (ASTM E 1354) |
28 MJ/kg |
Surface flammability NFPA 130 (ASTM E 162) |
passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) |
passed |
Smoke gas toxicity NFPA 130 (SMP 800C) |
passed |
Surge voltage test |
Result |
Test passed |
Temperature-rise test |
Requirement temperature-rise test |
Increase in temperature ≤ 45 K |
Result |
Test passed |
Result |
Test passed |
Power-frequency withstand voltage |
Test voltage setpoint |
1.89 kV |
Result |
Test passed |
Mechanical data |
Open side panel |
No |
Mechanical strength |
Result |
Test passed |
Attachment on the carrier |
Result |
Test passed |
Test for conductor damage and slackening |
Rotation speed |
10 (+/- 2) rpm |
Revolutions |
135 |
Conductor cross section/weight |
4 mm² / 0.9 kg |
Result |
Test passed |
Aging |
Temperature cycles |
192 |
192 |
192 |
Result |
Test passed |
Test passed |
Needle-flame test |
Time of exposure |
30 s |
Result |
Test passed |
Oscillation/broadband noise |
Spectrum |
Service life test category 2, bogie-mounted |
Frequency |
5 - 250 Hz |
ASD level |
6.12 (m/s²)²/Hz |
Acceleration |
3.12g |
Test duration per axis |
5 h |
Test directions |
X-, Y- and Z-axis |
Result |
Test passed |
Shocks |
Pulse shape |
Half-sine |
Acceleration |
30g |
Shock duration |
18 ms |
Number of shocks per direction |
3 |
Test directions |
X-, Y- and Z-axis (pos. and neg.) |
Result |
Test passed |
Ambient conditions |
Ambient temperature (operation) |
-60 °C ... 105 °C (max. short-term operating temperature RTI Elec.) |
Ambient temperature (storage/transport) |
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
Ambient temperature (assembly) |
-5 °C ... 70 °C |
Ambient temperature (actuation) |
-5 °C ... 70 °C |
Permissible humidity (storage/transport) |
30 % ... 70 % |
Connection in acc. with standard |
IEC 60947-7-3 |
Mounting type |
NS 35/7,5 |
NS 35/15 |