Công ty TNHH Kĩ thuật Thương mại Công nghệ MVN

Công ty TNHH Kĩ thuật Thương mại Công nghệ MVN

Hotline: 024 73061916

Menu
Hotline Tìm kiếm
Cầu đấu dây Phoenix Contact ST 4-HESILED 24 (5X20) 3036547

Cầu đấu dây Phoenix Contact ST 4-HESILED 24 (5X20) 3036547

Giá: Liên hệ

Cầu đấu dây Phoenix Contact ST 4-HESILED 24 (5X20) 3036547

Mã sản phẩm: 3036547

Mã hàng: ST 4-HESILED 24 (5X20)

Xuất xứ: Thổ Nhĩ Kỳ

Số lượng
  • Thông tin sản phẩm
  • Yêu cầu gửi báo giá

  • General The current is determined by the fuse used, the voltage by the selected LED.
    If the fuse is faulty, the downstream circuit will not be disconnected.

    Product type Fuse terminal block
    Number of connections 2
    Number of rows 1
    Potentials 1
    Insulation characteristics
    Overvoltage category III
    Degree of pollution 3

    Fuse type Glass / ceramics / ...
    Rated surge voltage 4 kV
    Maximum power dissipation for nominal condition 1.02 W
    Fuse G / 5 x 20
    LED voltage range 12 V AC/DC ... 30 V AC/DC
    LED current range 0.31 mA ... 0.95 mA
    Maximum power dissipation max. 1.6 W (with single arrangement of the fuse terminal block in the event of overload)
    max. 1.6 W (With interconnected arrangement of several fuse terminal blocks in the event of overload)
    max. 4 W (with single arrangement of the fuse terminal block in the event of a short-circuit)
    max. 2.5 W (With interconnected arrangement of several fuse terminal blocks in the event of a short-circuit)

    LED voltage range 12 V AC/DC ... 30 V AC/DC

    Number of connections per level 2
    Nominal cross section 4 mm²
    1 level
    Stripping length 8 mm
    Internal cylindrical gage A4
    Connection in acc. with standard IEC 60947-7-3
    Conductor cross section solid 0.08 mm² ... 6 mm²
    Cross section AWG 28 ... 10
    Conductor cross section flexible 0.08 mm² ... 4 mm²
    Conductor cross section, flexible [AWG] 28 ... 12
    Flexible conductor cross section flexible (ferrule, w/o plastic sleeve) 0.14 mm² ... 4 mm²
    Flexible conductor cross section (ferrule with plastic sleeve) 0.14 mm² ... 4 mm²
    2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve 0.5 mm² ... 1 mm²
    Nominal current 6.3 A
    Maximum load current 6.3 A (the current is determined by the fuse used)
    Nominal voltage 24 V
    Nominal cross section 1 mm²

    Width 6.2 mm
    Height NS 35/15 70 mm
    Height NS 35/7,5 62.5 mm
    Length 61.5 mm

    Color black
    Flammability rating according to UL 94 V0
    Insulating material group I
    Insulating material PA
    Static insulating material application in cold -60 °C
    Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) 130 °C
    Relative insulation material temperature index (Elec., UL 746 B) 130 °C
    Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 3
    Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 3
    Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 3
    Fire protection for rail vehicles (DIN EN 45545-2) R26 HL 1 - HL 3
    Calorimetric heat release NFPA 130 (ASTM E 1354) 28 MJ/kg
    Surface flammability NFPA 130 (ASTM E 162) passed
    Specific optical density of smoke NFPA 130 (ASTM E 662) passed
    Smoke gas toxicity NFPA 130 (SMP 800C) passed

    Surge voltage test
    Result Test passed
    Temperature-rise test
    Requirement temperature-rise test Increase in temperature ≤ 45 K
    Result Test passed
    Result Test passed
    Power-frequency withstand voltage
    Test voltage setpoint 1.89 kV
    Result Test passed

    Mechanical data
    Open side panel No

    Mechanical strength
    Result Test passed
    Attachment on the carrier
    Result Test passed
    Test for conductor damage and slackening
    Rotation speed 10 (+/- 2) rpm
    Revolutions 135
    Conductor cross section/weight 4 mm² / 0.9 kg
    Result Test passed

    Aging
    Temperature cycles 192
    192
    192
    Result Test passed
    Test passed
    Needle-flame test
    Time of exposure 30 s
    Result Test passed
    Oscillation/broadband noise
    Spectrum Service life test category 2, bogie-mounted
    Frequency 5 - 250 Hz
    ASD level 6.12 (m/s²)²/Hz
    Acceleration 3.12g
    Test duration per axis 5 h
    Test directions X-, Y- and Z-axis
    Result Test passed
    Shocks
    Pulse shape Half-sine
    Acceleration 30g
    Shock duration 18 ms
    Number of shocks per direction 3
    Test directions X-, Y- and Z-axis (pos. and neg.)
    Result Test passed
    Ambient conditions
    Ambient temperature (operation) -60 °C ... 105 °C (max. short-term operating temperature RTI Elec.)
    Ambient temperature (storage/transport) -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
    Ambient temperature (assembly) -5 °C ... 70 °C
    Ambient temperature (actuation) -5 °C ... 70 °C
    Permissible humidity (storage/transport) 30 % ... 70 %

    Connection in acc. with standard IEC 60947-7-3

    Mounting type NS 35/7,5
    NS 35/15

Các sản phẩm khác