Input:
AC operation | |
Nominal input voltage range | 100 V AC ... 240 V AC |
Input voltage range | 85 V AC ... 264 V AC |
Derating | < 100 V (1 %/V) |
Input voltage range AC | 85 V AC ... 264 V AC |
Input voltage range DC | 120 V DC ... 375 V DC |
Voltage type of supply voltage | AC |
Inrush current | typ. 40 A (115 V AC) |
typ. 80 A (230 V AC) | |
AC frequency range | 47 Hz ... 63 Hz |
Mains buffering time | typ. 10 ms (115 V AC) |
typ. 16 ms (230 V AC) | |
Current consumption | 5.4 A (115 V AC) |
2.7 A (230 V AC) | |
Nominal power consumption | 523.27 VA |
Protective circuit | Transient surge protection; Varistor |
Typical response time | 1000 ms |
Input fuse | 10 A (fast blow, internal) |
Discharge current to PE | < 1 mA (264 V AC) |
Output:
Efficiency | 85 % (115 V AC) |
88 % (230 V AC) | |
Output characteristic | HICCUP |
Nominal output voltage | 24 V DC ±2 % |
Setting range of the output voltage (USet) | 22 V DC ... 28 V DC (max. power ≤ 480 W) |
Nominal output current (IN) | 20 A |
Derating | > 40 °C (1.67 % / °C, 115 V AC) |
> 50 °C (2.5 % / °C, 230 V AC) | |
Max. capacitive load | 8000 μF |
Active current limitation | 109% - 130% of the max. output power (in the event of short circuit) |
Control deviation | ≤ 1 % (change in load, static 10 % ... 90 %) |
typ. ± 2 % (change in load, dynamic 10 % ... 90 %) | |
< 0.1 % (change in input voltage ±10 %) | |
Residual ripple | < 120 mVPP (-10 °C ... +70 °C) |
< 240 mVPP (-20 °C ... -10 °C) | |
Output power | 480 W |
Maximum no-load power dissipation | 5 W (115 V AC) |
4 W (230 V AC) | |
Power loss nominal load max. | 50 W (115 V AC) |
40 W (230 V AC) |