Efficiency |
> 92 % (UIN 96 V DC / UOUT 24 V DC) |
> 92 % (UIN 110 V DC / UOUT 24 V DC) |
Output characteristic |
U/I |
Nominal output voltage |
24 V DC ±1 % |
Setting range of the output voltage (USet) |
18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (IN) |
10 A (-40 °C ... 60 °C) |
POWER BOOST (IBoost) |
12.5 A (-40 °C ... 40 °C permanent, UOUT = 24 V DC) |
Selective Fuse Breaking (ISFB) |
60 A (12 ms) |
Magnetic circuit breaker tripping |
B2 / B4 / B6 |
Derating |
60 °C ... 70 °C (2.5%/K) |
Feedback voltage resistance |
35 V DC |
Protection against overvoltage at the output (OVP) |
< 35 V DC |
Max. capacitive load |
unlimited |
Active current limitation |
18 A |
Control deviation |
< 1 % (change in load, static 10 % ... 90 %) |
< 2 % (change in load, dynamic 10 % ... 90 %) |
< 0.1 % (change in input voltage ±10 %) |
Residual ripple |
< 20 mVPP |
Output power |
240 W |
Peak switching voltages nominal load |
< 10 mVPP (20 MHz) |
Maximum no-load power dissipation |
4 W (UIN 110 V DC) |
Power loss nominal load max. |
22 W (UIN 110 V DC) |
Rise time |
< 2 ms (UOUT (10 % ... 90 %)) |
Connection in parallel |
yes, for redundancy and increased capacity |
Connection in series |
yes |
Signal: DC OK active |
Output description |
UOUT > 0.9 x UN: High signal |
Switching voltage range |
18 V DC ... 24 V DC |
Maximum inrush current |
< 20 mA (short-circuit-proof) |
Signal: POWER BOOST, active |
Output description |
IOUT < IN: High signal |
Switching voltage range |
18 V DC ... 24 V DC |
Maximum inrush current |
< 20 mA (short-circuit-proof) |
Signal: UIN OK, active |
Output description |
UIN > 19.2 V: High signal |
Switching voltage range |
18 V DC ... 24 V DC |
Maximum inrush current |
≤ 20 mA (short-circuit-proof) |
Signal: DC OK floating |
Output description |
Relay |