Input data
Nominal input voltage range | 12 V DC ... 24 V DC |
Input voltage range | 12 V DC ... 24 V DC -25 % ... +33 % (SELV) |
Wide-range input | yes |
Electric strength, max. | 35 V DC (60 s) |
Inrush current | typ. 8.6 A |
Inrush current integral (I2t) | typ. 0.1 A2s |
Inrush current limitation | 8.6 A |
Mains buffering time | typ. 16 ms (24 V DC) |
Current consumption | typ. 7.2 A (12 V DC) |
typ. 3.5 A (24 V DC) | |
Switch-on time | < 1 s |
Input fuse | 15 A (fast blow, internal) |
Recommended breaker for input protection | 10 A ... 16 A (Characteristic B, C, D, K or comparable) |
Efficiency | typ. 92.1 % (24 V DC) |
Output characteristic | U/I Advanced |
Smart HICCUP | |
FUSE MODE | |
Nominal output voltage | 24 V DC |
Setting range of the output voltage (USet) | 24 V DC ... 28 V DC (> 24 V DC, constant capacity) |
Nominal output current (IN) | 2.5 A |
Static Boost (IStat.Boost) | 3.125 A (≤ 40 °C) |
Dynamic Boost (IDyn.Boost) | 5 A (≤ 60 °C (4.9 s)) |
Short-circuit-proof | yes |
No-load proof | yes |
Derating | > 60 °C (2.5%/K of POut nom.) |
Output power (PN) | 60 W |
Output power (PStat. Boost) | 75 W |
Output power (PDyn. Boost) | 120 W |
Feedback voltage resistance | ≤ 35 V DC |
Protection against overvoltage at the output (OVP) | ≤ 32 V DC |
Residual ripple | < 20 mVPP |
Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
Rise time | < 1 s (UOUT (10 % ... 90 %)) |
Connection in series | yes |
Maximum no-load power dissipation | < 1.3 W |
Power loss nominal load max. | < 8 W |
Connection in parallel | yes, for redundancy and increased capacity |
Signal (configurable) | |
Digital | 0 V DC |
24 V DC | |
22 mA | |
Default | 24 V DC |
22 mA | |
24 V DC for UOut > 0.9 x USet |