Efficiency |
typ. 92.2 % (12 V DC) |
Output characteristic |
U/I Advanced |
Smart HICCUP |
FUSE MODE |
Nominal output voltage |
12 V DC |
Setting range of the output voltage (USet) |
5 V DC ... 15 V DC (> 12 V DC, constant capacity) |
Nominal output current (IN) |
2.5 A |
Static Boost (IStat.Boost) |
3.125 A (≤ 40 °C) |
Dynamic Boost (IDyn.Boost) |
5 A (≤ 60 °C (4.9 s)) |
Short-circuit-proof |
yes |
No-load proof |
yes |
Derating |
> 60 °C (2.5%/K of POut nom.) |
Output power (PN) |
30 W |
Output power (PStat. Boost) |
37.5 W |
Output power (PDyn. Boost) |
60 W |
Feedback voltage resistance |
≤ 25 V DC |
Protection against overvoltage at the output (OVP) |
≤ 18 V DC |
Residual ripple |
< 20 mVPP |
Control deviation |
< 1 % (change in load, static 10 % ... 90 %) |
Control deviation |
< 1 % (change in load, static 10 % ... 90 %) |
Control deviation |
< 1 % (change in load, static 10 % ... 90 %) |
Rise time |
< 1 s (UOUT (10 % ... 90 %)) |
Connection in series |
yes |
Maximum no-load power dissipation |
< 0.5 W |
Power loss nominal load max. |
< 2.7 W |
Connection in parallel |
yes, for redundancy and increased capacity |
Signal (configurable) |
Digital |
0 V DC |
24 V DC |
22 mA |
Default |
24 V DC |
22 mA |
24 V DC for UOut > 0.9 x USet |