Efficiency |
> 93 % (120 V AC) |
> 94 % (230 V AC) |
Efficiency Level |
VI |
Nominal output voltage |
24 V DC |
Setting range of the output voltage (USet) |
22 V DC ... 27 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (IN) |
4 A |
Short-circuit-proof |
yes |
No-load proof |
yes |
Derating |
> 50 °C ... 70 °C (2 % / K) |
Crest factor |
typ. 1.74 |
typ. 2.08 |
Output power (PN) |
96 W |
Connection in parallel |
yes, for increasing power and redundancy with diode |
Connection in series |
yes, for increased output voltage |
Feedback voltage resistance |
≤ 35 V DC |
Protection against overvoltage at the output (OVP) |
< 35 V DC |
Residual ripple |
typ. 150 mVPP |
Control deviation |
< 0.5 % (Static load change 10 % ... 90 %) |
< 3 % (Dynamic load change 10 % ... 90 %, (10 Hz)) |
< 0.1 % (change in input voltage ±10 %) |
Rise time |
typ. 100 ms (UOut = 10 % ... 90 %) |
Minimum no-load power dissipation |
< 0.21 W (120 V AC) |
Maximum no-load power dissipation |
< 0.21 W (230 V AC) |
Minimum nominal load power dissipation |
< 7 W (120 V AC) |
Power loss nominal load max. |
< 5.7 W (230 V AC) |