Dimensions
Height 105.8 mm
Width 6.2 mm +0.1 mm
Depth 100 mm (incl. DIN rail 7.5 mm)
Back to top
Ambient conditions
Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 %
Altitude ≤ 4000 m (amsl (above mean sea level))
Degree of protection IP20
Back to top
General
Housing material PBT
Flammability rating according to UL 94 V-0
Color traffic grey A RAL 7042
light grey RAL 7035
Mounting type DIN rail: TH 35 - 7.5 mm
Type DIN rail module, two-section, divisible
Direction of action Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Back to top
Protective circuit
IEC test classification C1
C2
C3
D1
Nominal voltage UN 24 V DC
Maximum continuous voltage UC 30 V DC
21 V AC
Rated current 600 mA (56 °C)
Operating effective current IC at UC ≤ 5 µA
Residual current IPE ≤ 1 µA
Nominal discharge current In (8/20) µs (line-line) 5 kA
Nominal discharge current In (8/20) µs (line-earth) 5 kA
Pulse discharge current Iimp (10/350) µs (line-line) 0.5 kA
Pulse discharge current Iimp (10/350) µs (line-earth) 0.5 kA
Total discharge current Itotal (8/20) µs 10 kA
Voltage protection level Up (line-line) ≤ 200 V (C1 - 1 kV/500 A)
≤ 320 V (C2 - 10 kV / 5 kA)
≤ 50 V (C3 - 25 A)
≤ 55 V (C3 - 100 A)
Voltage protection level Up (line-earth) ≤ 750 V (C1 - 1 kV/500 A)
≤ 750 V (C2 - 10 kV / 5 kA)
≤ 700 V (C3 - 25 A)
≤ 750 V (C3 - 100 A)
Voltage protection level Up static (line-line) ≤ 50 V (C1 - 1 kV/500 A)
≤ 120 V (C2 - 10 kV / 5 kA)
Voltage protection level Up static (line-earth) ≤ 750 V (C1 - 1 kV/500 A)
≤ 750 V (C2 - 10 kV / 5 kA)
Response time tA (line-line) ≤ 1 ns