Dimensions
Width 124 mm
124 mm
Height 185 mm
210 mm
Depth 190 mm
190 mm
Note on dimensions without fan module
With fan module
Back to top
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) 0 °C ... 55 °C (from 45°C only with fan module)
Ambient temperature (storage/transport) -25 °C ... 70 °C
Permissible humidity (operation) 5 % ... 90 % (non-condensing)
Permissible humidity (storage/transport) 5 % ... 90 % (non-condensing)
Air pressure (operation) 80 kPa ... 108 kPa (up to 2000 m above sea level)
Air pressure (storage/transport) 66 kPa ... 108 kPa (up to 3000 m above sea level)
Shock 25g, Criterion 1, according to IEC 60068-2-27
Vibration (operation) 1g, Criterion 1, according to IEC 60068-2-6
Back to top
Control system
Engineering tool PC WORX
Programming languages supported Programming in acc. with IEC 61131-3
Diagnostics tool DIAG+ from version 1.14
Back to top
IEC 61131 runtime system
Engineering tool PC WORX
Program memory typ. 2 Mbyte (170 K instructions (IL))
Mass storage 4 Mbyte
Retentive mass storage 96 kByte (NVRAM)
Number of control tasks 16
Realtime clock Integrated (battery backup)
Back to top
Fieldbus function
Amount of process data max. 8192 Bit (INTERBUS-Master)
Number of supported devices max. 512 (of which 254 are remote bus devices/bus segments)
Number of devices with parameter channel max. 62
Program memory typ. 2 Mbyte (170 K instructions (IL))
Back to top
Data interfaces
Interface INTERBUS (Master)
Number 1
Connection method D-SUB-9 female connector
Transmission speed 500 kBaud / 2 MBaud (can be switched)
Interface Parameterization/operation/diagnostics
Number 1
Connection method D-SUB 9 plug
Interface Ethernet
Number 1
Connection method RJ45 jack
Transmission speed 10/100 Mbps
Interface Serial (RS-232)
Number 1
Connection method D-SUB 9 plug
Transmission speed 10/100 Mbps
Back to top
Direct I/Os
Input name Digital inputs
Number of inputs 5
Connection method Inline potential distributor
Connection technology 2, 3, 4-wire
Output name Digital outputs
Number of outputs 3
Connection method Spring-cage connection
Connection technology 2, 3, 4-wire
Maximum output current per channel 500 mA
Back to top
Power supply
Power supply connection Screw terminal blocks, plug-in
Typical current consumption 1.5 A
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (including ripple)
Residual ripple ±5 %
Power dissipation max. 20 W