Country of origin AT (Austria)
Dimensions
Width 45 mm
Height 90 mm
Depth 113 mm
Ambient conditions
Ambient temperature (operation) -25 °C ... 55 °C
-25 °C ... 40 °C (corresponds to UL 508)
Ambient temperature (storage/transport) -25 °C ... 70 °C
Permissible humidity (operation) 15 % ... 85 %
Degree of protection IP40 (Housing)
IP20 (Connection terminal blocks)
Input data
Nominal input voltage UN 480 V (3 N ~ 480/277 V)
Input voltage range 0 V AC ... 480 V AC (1(N) ~, single-phase load)
0 V AC ... 480 V AC (3(N) ~, 3-phase load)
Input current range 0.15 A ... 6 A (Range: 0.75 kW and 1.5 kW)
0.3 A ... 12 A (Range: 3 kW and 6 kW)
Overload capacity 12 A permanent
Maximum temperature coefficient ≤ 0.02 %/K
Function Underload, overload, window, winding temperature monitoring
Power supply
Supply voltage range 110 V AC ... 500 V AC (see Power modules)