Country of origin AT (Austria)
Dimensions
Width 22.5 mm
Height 90 mm
Depth 113 mm
Ambient conditions
Ambient temperature (operation) -25 °C ... 55 °C
-25 °C ... 40 °C (corresponds to UL 508)
Ambient temperature (storage/transport) -25 °C ... 70 °C
Permissible humidity (operation) 15 % ... 85 %
Degree of protection IP40 (Housing)
IP20 (Connection terminal blocks)
Noise immunity EN 61000-6-2
Input data
Input current range 0 mA ... 100 mA (Connection terminals: I1 and GND)
0 A ... 1 A (Connection terminals: I2 and GND)
0 A ... 10 A (Connection terminals: I3 and GND)
Overload capacity 800 mA (at IN = 100 mA)
3 A (at IN = 1 A)
12 A (at IN = 10 A)
Maximum temperature coefficient < 0.1 %/K
Function Overcurrent
Min. setting range 5 % ... 95 % (from IN)
Max. setting range 10 % ... 100 % (from IN)
Setting range for response delay 0.2 s ... 10 s
Basic accuracy ± 5 % (of scale end value)
Setting accuracy ≤ 5 % (of scale end value)
Repeat accuracy ≤ 2 %
Recovery time 500 ms
Power supply
Supply voltage range 24 V AC ... 230 V AC (see Power modules)
24 V DC (see Power modules)
Connection data
Connection method Screw connection
Stripping length 8 mm
Conductor cross section solid 0.5 mm² ... 2.5 mm²
Conductor cross section flexible 0.25 mm² ... 2.5 mm²
Conductor cross section AWG 20 ... 14
Tightening torque 1 Nm